PERMIT 2020-013357 EP
9503 RESEARCH BLVD NB BLDG 3 UNIT 300
Final
Electrical PermitRepairCommercial
Scope of work
Install new 277/480v 200 amp HV MLO panel 3/0 CU and #6 G feeder conductors and 2conduit from existing 277/480v 200 MCB disconnect new 75 kva transformer #1 #6G transformer primary feeder conductors and 1.5 conduit feeding existing 120/208v 200A LV MCB panel Transformer to meet requirements of 2017 NEC article 450.13 (B). Panel schedules required per 2017 NEC 408.4(A) Transformer disconnect to meet requirements of 2017 NEC article 450.14 OCPD requirements per 2017 NEC article 240.21 Load Calculations required for HV and LV panels No penetration of fire rated walls involved
Record
Permit number2020-013357 EP
StatusFinal
Applied01-29-20
Issued01-29-20
Expires08-03-20
Completed08-03-20
Valuation—
Housing units1