PERMIT 2026-036969 PP
804 WATERFALL WAY
Active
Plumbing PermitRepairResidential
Scope of work
Installed a gas pressure gauge on the gas system and pressurized the system to 7.5 PSI for testing. Performed a bubble test and found a gas leak beneath the fire pit at the 3/4 black iron fittings. Removed the failed fittings and replaced them with new fittings. Also found a leak at the pool heater union which was replaced as well. After completing the repairs all repaired gas piping and fittings were coated with gray spray paint for protection. 804 Waterfall Way Austin TX 78753
Record
Permit number2026-036969 PP
StatusActive
Applied03-27-26
Issued04-03-26
Expires10-07-26
Completed—
Valuation—
Remodel sqft2,794
Council district1
Official recordCity of Austin →
⚡ Alerts for work like this
Every new Plumbing Permit permit in 78753, in your inbox the morning it’s issued.
Set alert · Pro