517 S PLEASANT VALLEY RD
Scope of work
Electrical connection to existing water quality control pond pump at Krieg Field (City of Austin Parks and Recreation). Install approximately 345 linear feet of electrical conduit from an existing panel to the existing pump electrical connection point. Install one 15-amp 480-volt 1-phase circuit from existing 480-volt panel to a location near the pump controller. At the pump controller location install one rack-mounted 7kVA 480-120/240-volt transformer with service disconnects for line and load connections. Terminate new low-voltage circuit to the pump controller. Underground feeder routed in 2 Schedule 80 PVC from the 480-volt panel to the transformer with two in-ground Quazite boxes with lids. Conductor size increased based on limiting voltage drop due to length. Pump controller and alarm system provided by others and existing. Trenching provided by City of Austin Parks and Recreation.